← Library
B01Energy(Balance)Signature
Ready on booking
HVAC, lights and blinds reach comfort 15 minutes before a booked meeting, sized to its attendees, with a fresh-air flush before the first booking of the day
Readiness
1 Located
Release wave
Launch (Jan 2027)
Group
Rooms and floors
Risk tier
R3
Autonomy at design
Advise
Autonomy at launch
Advise
Version
2.0.0
Settings: Lead minutes, band per space type
Serve
Who benefits
Meeting attendees
Adverse experience to avoid
Arriving to a room that is too hot or stuffy
Authority
System owners
BMS owner
Declared scopes
A18
Flow
When
Triggers
T07Before booking startAll
15 minutes before a booked meeting
If
Context
C19Comfort bandComfort
Room comfort band
TTL 120s · on unknown: skip
C23BMS point stateComfort
Current room state
TTL 120s · on unknown: skip
Then
Ask and act
A18BMS scenes4All
Setpoint, lights and blinds for the attendees
RiskR3
Conflict key
zone:{zone}:hvac
Compensation
restore the prior BMS state within bounds
Retry safe
Yes within bounds
Verify
Read-back
V04BMS read-backs5All
Read back
Evidence
Time stage
Meet
Metric
Minutes adjusting room comfort avoided
Basis
Modelled
Evidence grade
Modelled
Fallback on failure
Native system keeps control; play pauses, holds its claim and notifies the system owner