B03Energy(Balance)Experience
Occupancy mode
Writes the BMS occupancy mode per zone from a four-state space matrix with data freshness: Booked to Standby, Occupied to Occupied, Free or Ghost to Unoccupied; a manual BMS override always wins
Readiness
1 Located
Release wave
Wave 2 (Q1 2027)
Group
Rooms and floors
Risk tier
R3
Autonomy at design
Autonomous
Autonomy at launch
Ask
Version
2.0.0
Settings: Mode per state, delays, Night and weekend setback values (was B25); seasonal bands and dates (was B30); override expiry hours (was B31)
Serve
Who benefits
Occupants of every zone
Adverse experience to avoid
Comfort set back while people are still there
Authority
System owners
BMS owner
Declared scopes
A18
Flow
When
Triggers
T26Space state changedAll
Booked, Occupied, Free or Ghost
If
Context
C19Comfort bandAll
Band
TTL 120s · on unknown: skip
Then
Ask and act
A18BMS scenes3All
Write the BMS occupancy mode
RiskR3
Conflict key
zone:{zone}:hvac
Compensation
restore the prior BMS state within bounds
Retry safe
Yes within bounds
Verify
Read-back
V04BMS read-backs4All
Read back
Evidence
Time stage
None
Metric
None
Basis
None
Evidence grade
Observed (state change)
Fallback on failure
Native system keeps control; play pauses, holds its claim and notifies the system owner