← Library
B10Energy(Balance)Signature
Arrival-aware start
The first badge or plate starts the floor, not a fixed 06:00; a late booking or after-hours entry conditions only that zone, with an end time
Readiness
1 Located
Release wave
Wave 3 (Q2 to Q3 2027)
Group
Rooms and floors
Risk tier
R3
Autonomy at design
Autonomous
Autonomy at launch
Ask until site certified
Version
2.0.0
Settings: Earliest start, fallback time, End time, zones, Start sequence and gaps for AHUs and chillers (was B20)
Serve
Who benefits
Early arrivals and after-hours workers
Adverse experience to avoid
Arriving to an unconditioned floor
Authority
System owners
BMS owner
Declared scopes
A18
Flow
When
Triggers
T21Access eventAll
First badge or plate of the day
If
Context
C19Comfort bandAfter hours
Band
TTL 120s · on unknown: skip
Then
Ask and act
A18BMS scenes3All
Start the floor
RiskR3
Conflict key
zone:{zone}:hvac
Compensation
restore the prior BMS state within bounds
Retry safe
Yes within bounds
Verify
Read-back
V04BMS read-backs4All
Read back
Evidence
Time stage
None
Metric
None
Basis
None
Evidence grade
Observed (state change)
Fallback on failure
Native system keeps control; play pauses, holds its claim and notifies the system owner