B12Energy(Balance)Signature

Air on demand

Modulates fresh air to CO₂, TVOC and occupancy within the certified fresh-air limits; on dust days caps fresh air at the certified minimum, never below; flags humidity before condensation or mould

Simulate
Readiness
0 Concept
Release wave
Wave 3 (Q2 to Q3 2027)
Group
Air and wellbeing
Risk tier
R3
Autonomy at design
Autonomous
Autonomy at launch
Ask
Version
2.0.0

Settings: Fresh-air min and max, CO₂ and TVOC targets, PM2.5 threshold, RH band

Serve

Who benefits
Everyone breathing indoor air
Adverse experience to avoid
Fresh air reduced below safe minimums

Authority

System owners
BMS owner, FM owner
Declared scopes
A01A16A18

Flow

When
Triggers
T18Environment thresholdIndoor air, Humidity

CO₂ or TVOC change

T25Weather or outdoor airDust day

Outdoor PM2.5 high

If
Context
C21Environment readingIndoor air

IAQ per zone

TTL 120s · on unknown: skip

C09Live occupancyIndoor air

People count

TTL 120s · on unknown: skip

C19Comfort bandIndoor air

Fresh-air limits

TTL 120s · on unknown: skip

Then
Ask and act
A18BMS scenes6Indoor air, Dust day

Cap fresh air at the certified minimum, never below it

RiskR3
Conflict key
zone:{zone}:hvac
Compensation
restore the prior BMS state within bounds
Retry safe
Yes within bounds
A16Raise tickets8Indoor air, Humidity

Damper or filter ticket if not

RiskR1
Conflict key
ticket:{asset}:{category}
Compensation
cancel the ticket
Retry safe
Yes with key
A01Notifys9Dust day, Humidity

Tell occupants

RiskR0
Conflict key
none
Compensation
none
Retry safe
Yes with dedup
Verify
Read-back
V09Environment back in bands7All

CO₂ under target within 15 minutes

Evidence

Time stage
None
Metric
None
Basis
None
Evidence grade
Observed (state change)
Fallback on failure