← Library
B32Energy(Balance)Experience
Waste watch
Energy and water waste caught as it happens: a door held open on a cooled zone, a zone cooled with nobody in it, night baseload creeping up, a leak or abnormal night flow
Readiness
0 Concept
Release wave
Wave 3 (Q2 to Q3 2027)
Group
Waste and faults
Risk tier
R3
Autonomy at design
Autonomous
Autonomy at launch
Ask until site certified
Version
2.0.0
Settings: Held-open minutes, Vacant hours, Baseline, threshold, Night flow threshold
Serve
Who benefits
Facilities and sustainability
Adverse experience to avoid
Corrective action that disrupts occupied zones
Authority
System owners
BMS owner, FM owner
Declared scopes
A01A16A18
Flow
When
Triggers
T18Environment thresholdDoor open, Water
Contact held open
T09Count or occupancy thresholdEmpty zone
Vacant 2 hours
T06ScheduleNight baseload
Nightly
If
Context
C23BMS point stateDoor open, Empty zone
Zone cooling
TTL 120s · on unknown: skip
C22Meter and baselineNight baseload
Night load against baseline
TTL 120s · on unknown: skip
Then
Ask and act
A01Notifys6All
Alert
RiskR0
Conflict key
none
Compensation
none
Retry safe
Yes with dedup
A18BMS scenes7Door open, Empty zone
Setback the zone
RiskR3
Conflict key
zone:{zone}:hvac
Compensation
restore the prior BMS state within bounds
Retry safe
Yes within bounds
A16Raise tickets10Water
Work order
RiskR1
Conflict key
ticket:{asset}:{category}
Compensation
cancel the ticket
Retry safe
Yes with key
Verify
Read-back
V06Outcome metrics9Night baseload
Baseload trend
V04BMS read-backs8Door open, Empty zone
Read back
V08Ticket closeds11Water
Ticket closed
Evidence
Time stage
None
Metric
None
Basis
None
Evidence grade
Observed (state change)
Fallback on failure
Native system keeps control; play pauses, holds its claim and notifies the system owner